Optically isolated inputs are arranged such that each group of four shares a single common.
The four I/O points and shared common are connected via a five-position removable screw
terminal. Input voltage range is 5-30VDC. Like the inputs, each group of four Reed relays also
shares a single common and connects via a five-position removable screw terminal. Form C
Relay outputs are arranged such that each group of two relays shares a common. The NC and
NO contacts of each relay along with the common are brought out via a five-position removable
screw terminal.